TM 9-6115-730-24
0083
REPROGRAMMING OR VERIFYING DVR PARAMETERS - Continued
Table 2. 200 kW TQG DVR Programming Parameters.
TQG SETPOINTS
TQG SETPOINTS
240/216
120/206
DESCRIPTION
PARAMETER
ACTION
UNITS
60 Hz
50 Hz
60 Hz
50 Hz
:01
Program
Volts
434
410
217
205
Voltage
Ratio of output volts
:02
Program
2.0
2.0
1.0
1.0
to sensing volts
Generator type
:03
Program
0
0
0
0
:04
Program
Ampere
347
289
694
578
Output Current
CT Voltage at Rated
:05
Program
Volts
4.34
3.61
4.34
3.61
Output Current
:06
Program
Hz
58.8
49.8
58.8
49.8
Decreasing Volts/Hz
:07
Program
Volts/Hz
3.0
3.0
3.0
3.0
Slope 1
Decreasing Volts/Hz
:08
Program
Volts/Hz
2.0
2.0
2.0
2.0
Slope 2
Minimum Voltage
:09
Program
%
50.0
50.0
50.0
50.0
:10
Program
Hz
25.0
25.0
25.0
25.0
Point
Overvoltage Trip
:11
Program
%
125.0
125.0
125.0
125.0
Point
Overvoltage Trip
:12
Program
Seconds
2
2
2
2
Time
Under Voltage Trip
:13
Program
%
75
75
75
75
Point
Under Voltage Trip
:14
Program
Seconds
30
30
30
30
Time
Voltage Gain (IR
:15
Program
%
0
0
0
0
Compensation)