TM 9-6115-730-24
0083
REPROGRAMMING OR VERIFYING DVR PARAMETERS
The following procedure is used to reprogram the DVR if a DVR is replaced or if there is some reason to verify
DVR parameters. Table 2 describes the parameters and lists values to be programmed or verified.
1. Set Battery Disconnect Switch to ON.
2. Set DEAD CRANK SWITCH to NORMAL.
3. On EMCP, set ENGINE CONTROL switch to COOL DOWN/STOP.
4. Select reprogramming data or parameter to be verified from Table 2.
5. DVR display should read :01 (the colon with the number indicates that the number is a parameter number).
6. Press and hold up arrow key
until display shows parameter number :90.
7. Press Function
key on DVR once to display data for parameter :90
0083-3