TM 9-6115-730-24
0083
REPROGRAMMING OR VERIFYING DVR PARAMETERS - Continued
Table 2. 200 kW TQG DVR Programming Parameters - Continued.
TQG SETPOINTS
TQG SETPOINTS
240/216
120/206
DESCRIPTION
PARAMETER
ACTION
UNITS
60 Hz
50 Hz
60 Hz
50 Hz
Integral Gain
:16
Program
3.0
3.0
3.0
3.0
Proportional Gain
:17
Program
1.0
1.0
1.0
1.0
Single Phase
:18
Program
0000
0000
0000
0000
Sensing 3ph=0
1ph=1
:19
Program
Ampere
2.0
2.0
2.0
2.0
Point
Reverse VAR Trip
:20
Program
Seconds
.5
.5
.5
.5
Time
Reverse VAR Fault
:21
Program
2
2
2
2
Selection
Droop/CCC Select
:22
Program
0
0
0
0
0+D 1=CCC
Droop Percentage
:30
Program
%
1.8
1.8
1.8
1.8
Reverse Power
:34
Program
%
20
20
20
20
Trip Point
Reverse Power
:35
Program
Seconds
7
7
7
7
Trip Time
:50
View
Hz
Voltage
:51
View
Volts
Current
:52
View
Ampere
Reactive Output
:53
View
Ampere
Current
:54
View
Ampere
Current
0083-5