TM 9-6115-730-24
0083
REPROGRAMMING GSC SETPOINTS FOR VOLTAGE AND FREQUENCY CHANGE - Continued
22. Repeat steps 18 through 21 until all setpoint values are checked or changed for OP5-0.
23. Repeat steps 16 through 22 for OP5-1. The first setpoint displayed will be P101. The first setpoint to be
changed/verified is P114, per Table 3.
24. At the completion of the programming, press EXIT key until SERV is no longer displayed on upper display.
25. If the generator set is not to be used, set ENGINE CONTROL switch to OFF/RESET, set DEAD CRANK
SWITCH to OFF, and set Battery Disconnect Switch to OFF.
END OF TASK
REPROGRAMMING OR VERIFYING GSC SETPOINTS
The following procedure is used to reprogram the GSC if a GSC is replaced or if there is some reason to verify
GSC setpoints as part of troubleshooting or analysis. Table 4 describes 200 kW OP5-0 Engine/Generator Setpoint
Programming and lists values to be programmed or verified. Table 5 describes OP5-1 Protective Relaying Setpoint
Programming and lists values to be programmed or verified. Table 6 describes OP5-3 Synchronization Setpoint
Programming and lists values to be programmed or verified. Table 7 describes OP6-0 Spare Input/Output Setpoint
Programming. Table 8 describes OP8 data from ATB and BTB transformers in the control panel that must be
entered if either of those devices is replaced.
1. Set Battery Disconnect Switch to ON.
2. Set DEAD CRANK SWITCH to NORMAL.
3. On EMCP, set ENGINE CONTROL switch to COOL DOWN/STOP.
4. Select programming data for GSC from Tables 4 thru 8 for GSC programming to be verified or completed. If
GSC has been replaced, all setpoints must be verified or reprogrammed. Factory default values must be
verified and TQG custom values must be programmed.
NOTE
In SERVICE MODE, the buttons on the GSC keypad perform new functions as follows:
POWER METER is Scroll Right
AC METER is Scroll Up
ENGINE METER is Scroll Down
LAMP TEST is Select
ALARM CODES is Enter
5. Press SERVICE MODE key on GSC. SERV will be displayed on upper display. OP1 will be displayed on
lower display.
6. Press AC METER key five times. OP3 will be displayed.
7. Press the LAMP TEST key. P E ---------- will be displayed. The left-most underline will be flashing. If an error
is made any time during the password entry, P E FAIL will be displayed. Password entry can be restarted by
pressing LAMP TEST key.
8. Press POWER METER key. P E 1 _ _ _ _ will be displayed. The left-most underline will be flashing.