TM 9-6115-730-24
0083
REPROGRAMMING OR VERIFYING GSC SETPOINTS - Continued
Table 4. 200 kW OP5-0 Engine/Generator Setpoint Programming - Continued.
240/416
120/208
FACTORY
60 Hz
60Hz
(50 Hz) 8
DESCRIPTION
RANGE OF VALUES
DEFAULT
(50 Hz)
P019 Cooldown Time:
0 to 30 minutes in increments of
5 min
5 min
5 min
Amount of time GSC allows
1 minute.
the engine to run after a
normal shutdown is initiated.
P020 AC Voltage: Nominal
700, 150, 300, 500, 600, 750,
700
700
700
AC voltage of generator. The
3.0k, 4.5k, 5.20k, 5.25k, 9.0k,
GSC measures and displays
15.0k, 18.0k, 30.0k
the AC voltage. 4
P021 AC Current Full Scale:
75, 100, 150, 200, 300, 400,
600
800
800
Nominal full scale AC current
600, 800, 1000, 1200, 1500,
2000, 2500, 3000, and 4000A
scale is equal to ratio of
in generator housing.
P022 GSC Engine Number:
01 through 08
01
01
01
Informs other devices on the
CAT Data Link of the engine
number for GSC. 5
P023 Engine Type:
0 MUI diesel
0
2
2
Identifies the engine as a
1 Gas
mechanical unit injector (MUI)
2 EIU diesel
diesel, spark ignited (gas), or
electronic unit injector (EUI)
diesel engine.
____________
4
The values other than the default (700V) are for switch gear applications and require the use of external
potential transformers and the removal of the AC voltage range jumper located in the relay module. See the topic
AC Voltage Range Selection in the Testing and Adjusting section.
5
After setpoint P022 is reprogrammed, GSC must be power cycled (powered down and then powered up).
8
Setpoint to be changed from factory defaults to 200 TQG setpoints at switch gear supplier.
0083-14