TM 9-6115-730-24
0083
REPROGRAMMING OR VERIFYING GSC SETPOINTS - Continued
Table 4. 200 kW OP5-0 Engine/Generator Setpoint Programming - Continued.
240/416
120/208
FACTORY
60 Hz
60Hz
(50 Hz) 8
DESCRIPTION
RANGE OF VALUES
DEFAULT
(50 Hz)
P030 Nameplate Power:
0 through 10 MW in increments
400 kW
200 kW
200 kW
Rated power capability of
of 1 kW
(166 kW)
(166 kW)
generator.
50 or 60 Hz
60 Hz
60 Hz
60 Hz
(50 Hz)
(50 Hz)
TQG.
P032 Connection
0 Wye
0
0
0
Configuration of Generator:
1 Delta
Wye or Delta configuration of
generator.
P033 Number of Generator
0 through 254 in increments of 2
4
4
4
Poles. 6
1
The setpoints (stored or being programmed) must match the specified setpoints of the TQG.
6
When P033 is programmed to 0 poles, the AL15 (GSC Configuration Error) fault is disabled.
8
Setpoints to be changed from factory defaults to 200 TQG setpoints at switch gear supplier.
Table 5. OP5-1 Protective Relaying Setpoint Programming.
FACTORY
SETPOINTS
60 Hz (50 Hz) 3
DESCRIPTION
RANGE OF VALUES
DEFAULT
P101 Generator Overvoltage Alarm
0 disabled
1
1
Enable: GSC enables or disables
1 enabled
P102 Generator Overvoltage Alarm
100 to 125% of nameplate
105%
125%
Threshold: Voltage GSC uses to issue
voltage in increments of 1%
overvoltage alarm.
0 through 120 seconds 2 in
P103 Generator Overvoltage Alarm
10 sec
0 sec
Time Delay: Amount of time the FSC+
increments of 1
waits before issuing overvoltage alarm.
____________
2
When programmed to 0 seconds, the actual time is from 0.5 to 1.0 seconds.
3
Setpoints to be changed from factory defaults to 200 TQG setpoints at switch gear supplier.
4
Setpoint values for disabled parameters are for fail safe/pack purposes.