TM 9-6115-730-24
0083
REPROGRAMMING OR VERIFYING GSC SETPOINTS - Continued
Table 4. 200 kW OP5-0 Engine/Generator Setpoint Programming.
240/416
120/208
FACTORY
60 Hz
60Hz
(50 Hz) 8
DESCRIPTION
RANGE OF VALUES
DEFAULT
(50 Hz)
0
0
0
used on the TQG.
P002 Units Shown: Type of
0 for English units (psi, F)
0
0
0
measurement units shown on
1 for metric units (kPa, C)
the GSC display.
P003 Shutdown Override for
0 for engine shutdown
0
0
0
Engine Fault: GSC response
1 for alarm only (shutdown
to a low engine oil pressure or
override, no engine shutdown)
high coolant temperature fault.
P004 Shutdown Override
0 for alarm only (shutdown
0
0
0
For Sensor Fault: GSC
override, no engine shutdown)
response to a diagnostic fault
1 for engine shutdown
with the engine oil pressure
sensor, coolant temperature
sensor, oil temperature
sensor, sensor power supply,
or coolant loss sensor.
P005 Coolant Loss Sensor
0 for TQGs without a coolant
0
1
1
Installed: Tells whether or not
loss sensor
the optional engine coolant
1 for TQGs with coolant loss
loss sensor is installed on the
sensor
TQG.
P006 Shutdown Override for
0 for engine shutdown
0
1
1
Coolant Loss Fault: GSC
1 for alarm only (shutdown
response to an engine coolant
override, no engine shutdown)
loss fault.
P007 System Voltage, 24 or
24 or 32
24
24
24
32 Volts: System voltage
(battery voltage) of the TQG.
P008 This setpoint is not
N/A
N/A
N/A
N/A
currently being used by GSC
and cannot be programmed.
____________
8
Setpoints to be changed from factory defaults to 200 TQG setpoints at switch gear supplier.