TM 9-6115-730-24
0083
REPROGRAMMING OR VERIFYING GSC SETPOINTS - Continued
9. Press ENGINE METER key. P E 1 3 _ _ _ will be displayed. The left-most underline will be flashing.
10. Press AC METER key. P E 1 3 2 _ _ will be displayed. The left-most underline will be flashing.
11. Press ENGINE METER key. P E 1 3 2 3 _ will be displayed. The underline will be flashing.
12. Press POWER METER key. P E 1 3 2 3 1 will be displayed.
13. Press ALARM CODES key. P E PASS will be displayed.
14. Press EXIT key. OP4 will be displayed.
15. Press AC METER key. OP5 will be displayed.
NOTE
For input values the OP set and the parameter values will toggle between the upper and lower
displays as each OP set is entered.
16. Press AC METER key or ENGINE METER key until OP5-0 is displayed.
17. Press LAMP TEST key. P001 will be displayed followed by the value of the setpoint.
18. Press ENGINE METER key until next setpoint to be verified or changed is displayed.
19. Press LAMP TEST key. The value of the setpoint will begin to flash.
20. Press AC METER key or ENGINE METER key to change the value, as required, to what is shown in Table 4
corresponding to the desired setpoint value.
21. Press ALARM CODES key. The value of the setpoint will stop flashing.
22. Repeat steps 18 through 21 until all setpoint values are checked or changed for OP5-0.
23. Repeat the process in steps 16 through 22 for OP5-1. The first setpoint displayed for OP5-1 will be P101. The
first setpoint to be changed/verified is P101 per Table 5.
24. Repeat the process in steps 16 through 22 for OP5-3. The first setpoint displayed for OP5-3 will be P301. The
first setpoint to be changed/verified is P301, per Table 6.
25. Repeat the process in steps 16 through 22 for OP6-0. The first setpoint displayed for OP6-0 will be SP01. The
first setpoint to be changed/verified is SP01 per Table 7.
26. At the completion of the programming, press EXIT key until SERV is no longer displayed on upper display.
27. If the generator set is not to be used, set ENGINE CONTROL switch to OFF/RESET, set DEAD CRANK
SWITCH to OFF, and set Battery Disconnect Switch to OFF.
0083-10