TM 9-6115-729-10
0012 00
PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS), INCLUDING LUBRICATION
INSTRUCTIONS Continued
Table 1. Preventive Maintenance Checks and Services Continued.
LOCATION/
NOT FULLY
ITEM TO
MISSION
ITEM
NO.
INTERVAL
CHECK/SERVICE
PROCEDURE
CAPABLE IF:
__________
ENGINE
WARNING
COMPARTMENT
Continued
flammable. Do not smoke or use open
flames when performing maintenance.
Failure to comply can result in flames
and possible explosion and can cause
injury or death to personnel and
damage to the generator set.
NOTE
ENGINE
COMPARTMENT
Continued
If the TQG is operating continuously, do
the DURING checks every four hours.
Inspect fuel system for leaks, damaged,
34
During
Fuel System
Any fuel leaks,
loose or missing parts.
damaged, loose or
missing parts.
35
During
Lubrication System
Inspect lubrication system for leaks,
Class III leaks.
damaged, loose or missing parts.
Damaged, loose or
missing parts.
Oil level is below hot
add oil level mark
on dipstick.
COOLING
SYSTEM
__________
WARNING
Cooling system operates at high
temperature and pressure. When
performing DURING PMCS, wear
gloves and additional protective clothing
and goggles as required. Contact with
high pressure steam and/or liquids can
result in burns and scalding.
36
During
Cooling Fan
Check for unusual noise being emitted from
Cooling fan is
fan area.
damaged or loose.
37
During
Overflow Bottle
Check coolant level between COLD and
Coolant level is below
HOT lines in overflow bottle
COLD line.
0012 00-12