TM 9-6115-729-10
100 kW TACTICAL QUIET GENERATOR SET
0012 00
PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS), INCLUDING LUBRICATION
INSTRUCTIONS Continued
Table 1. Preventive Maintenance Checks and Services Continued.
LOCATION/
NOT FULLY
ITEM TO
MISSION
ITEM
NO.
INTERVAL
CHECK/SERVICE
PROCEDURE
CAPABLE IF:
__________
26
Before
Ground Rod Cable
WARNING
and Connection
High voltage is produced when the
generator set is in operation. Never
it is properly grounded. Failure to
comply can cause injury or death to
personnel.
Inspect ground rod and cable for loose
Any missing or
connections, breaks, damage and
damaged parts.
corrosion.
PU-807A TRAILER
INSTALLATION
27
Before
Identification plates
If generator set is trailer-mounted (PU-
807A), check to ensure identification
plates on trailer are secure.
28
Before
Fire Extinguisher
Fire extinguishers are
Verify that two fire extinguishers are
not present or not
mounted to trailer brackets and are fully
certified. Needle is
charged.
not in green zone.
Check that fire extinguisher needle (if
applicable) is in green zone.
Check fire extinguisher seal. If seal is
broken or missing, replace fire
extinguisher.
Visually inspect bracket for obvious
damage.
__________
29
Before
Ground Rod Cable
WARNING
and Connection
High voltage is produced when this
generator set is in operation. Make sure
unit is completely shut down and free of
any power source before attempting any
repair or maintenance on the unit.
Failure to comply can cause injury or
death to personnel.
Inspect ground rod, grounding cable to
Any missing or
trailer terminal, and grounding cable to
damaged parts.
Connections are loose
breaks, damage and corrosion.
or corroded.
0012 00-9