TM 9-6115-729-10
0012 00
PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS), INCLUDING LUBRICATION
INSTRUCTIONS Continued
Table 1. Preventive Maintenance Checks and Services Continued.
LOCATION/
NOT FULLY
ITEM TO
MISSION
ITEM
NO.
INTERVAL
CHECK/SERVICE
PROCEDURE
CAPABLE IF:
15
Before
Overflow Bottle
Check overflow bottle for leaks, cracks, or
Class III leaks or
missing parts.
overflow bottle
missing.
Check coolant level above COLD line in
Coolant level is below
COLD line.
16
Before
Exhaust System
corrosion, damaged, or missing parts.
system have
missing parts.
Check exhaust system for restrictions and
Restricted exhaust
proper venting to atmosphere.
17
Before
Air Cleaner
Inspect air cleaner assembly and piping for
Clogged element is
Assembly
loose or damaged connections.
indicated (red),
piping and
Check restriction indicator for clogged
connections loose,
restriction indicator
broken or missing.
__________
18
Before
Battery Cables
WARNING
electrical components even with
generator set shut down. Avoid
shorting any positive with
ground/negative. Failure to comply can
cause injury to personnel and damage to
equipment.
Inspect cables and connectors for corrosion,
Cables are loose,
loose, damaged or missing parts.
damaged or
missing.
Batteries fail to start
generator.
19
Before
Output Load
Check for loose or damaged wiring or load
Loose or damaged
Terminal Board
cables inside generator set.
wiring or cables.
Check output terminals for damaged, loose
Damaged, loose or
or missing hardware.
missing hardware.
20
Before
Reconnection Board
Verify position of Reconnection Board and
Reconnection Board
check to see if it is in the correct position
is set for incorrect
for voltage outputs required by load.
voltage output.
Notify maintenance if repositioning is
required.
0012 00-7