TM 9-6115-729-10
100 kW TACTICAL QUIET GENERATOR SET
0012 00
PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS), INCLUDING LUBRICATION
INSTRUCTIONS Continued
Table 1. Preventive Maintenance Checks and Services Continued.
LOCATION/
NOT FULLY
ITEM TO
MISSION
ITEM
NO.
INTERVAL
CHECK/SERVICE
PROCEDURE
CAPABLE IF:
CONTROL PANEL
ASSEMBLY
__________
WARNING
and become entangled in generator set
components. Remove all metal jewelry
to comply can cause injury or death to
personnel.
DC voltages are present at generator set
electrical components even with
generator set shut down. Avoid
shorting any positive with
ground/negative. Failure to comply can
cause injury to personnel and damage to
equipment.
Set DEAD CRANK SWITCH to NORMAL
Set Battery Disconnect Switch to ON (WP
Set ENGINE CONTROL switch to COOL
21
Before
Indicators and
Check all indicators and controls for
Indicators or controls
Controls
damaged or missing parts.
damaged or
missing.
22
Before
Control Panel Wiring
Check for loose or damaged wiring or
Loose or damaged
Harness
connectors.
wiring or
connectors.
23
Before
Generator Set
Touch LAMP TEST on keypad and check
GSC indicator lights
Control
that all eight indicator lights on GSC and
and display
upper and lower display segments light.
segments do not
light.
24
Before
Alarm Module
Press LAMP TEST and check that alarm
Alarm Module lights
indicators light and alarm sounds.
do not light and
alarm does not
sound.
25
Before
Parallel Cable
Parallel cable missing
inspect parallel cable for damage.
or damaged.
0012 00-8