TM 9-6115-729-10
0012 00
PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS), INCLUDING LUBRICATION
INSTRUCTIONS Continued
Table 1. Preventive Maintenance Checks and Services Continued.
LOCATION/
NOT FULLY
ITEM TO
MISSION
ITEM
NO.
INTERVAL
CHECK/SERVICE
PROCEDURE
CAPABLE IF:
41
During
Overall Exterior
Check external doors, panels, hinges, and
Cannot shut doors.
latches for damaged, loose or corroded
items.
CAUTION
Operating the generator set with
restricted airflow for cooling can cause
the generator set to overheat. Keep all
access door inlet panels clear to ensure
maximum airflow for engine and
generator cooling. Failure to comply
can result in poor engine performance
and possible overheating and automatic
shutdown.
Any restriction of air
Inspect air intake and exhaust grills for
flow or cannot clear
debris.
debris.
ENGINE
COMPARTMENT
After
Engine Assembly
Hardware loose,
42
Check for loose damaged or missing
damaged, or
hardware.
missing.
__________
43
After
Fuel System
WARNING
flammable. Do not smoke or use open
flames when performing maintenance.
Failure to comply can result in flames
and possible explosion and can cause
injury or death to personnel and
damage to the generator set.
Inspect fuel system for leaks, damaged,
Any fuel leaks,
loose or missing parts.
damaged, loose or
missing parts.
44
After
Fuel Filter/Water
Inspect fuel filter/water separator for leaks,
Any fuel leaks,
Separator
proper mounting, cracks, damage, or
cracks, or missing
missing parts.
parts.
Drain water from fuel filter/water separator
Fuel filter/water
separator contains
sediment and/or
water or cannot be
drained.
0012 00-14