TM 9-6115-650-14&P
(b) Slide terminal (9) at free end of wire onto load terminal stud (8) and secure with flat washer (7) and
nut (6).
(c) Position cover (4) on switch box (5) and secure with 16 screws
washers (3).
(1), 16 Iockwashers (2) and 16 flat
d. Power Cable Replacement. (See figure 4-12.) There are two power cables on the power plant - one for
each generator set. This procedure is typical for both. When attaching wires, refer to the schematic inside the
switch box (figure 4-7) and to the identification bands on each of the five wires that make up each cable.
(1) Removal.
(a)
Disconnect power cable from load terminals on generator set. (Refer to paragraph 4-1, a (12).)
(c)
Figure 4-12. Power Cable Replacement.
(b)
Remove 16 screws (1), 16 Iockwashers (2) and 16 flat washers (3) securing cover (4) to switch box
(5) and take cover off switch box.
NOTE
Tag switch terminals for identification when removing wires. If identification bands on
wires are illegible, tag wires.
Remove screw (6), nut (7) and star washer (8) attaching each of three wires (9) (black, red and blue)
to its respective switch terminal (10). Take off wires.
4-25