TM 9-6115-650-14&P
(d)
(e)
(f)
Remove nut (11 ) and flat washer(12) from load terminal LO (13) inside switch box (5). Take off white
wire (14) associated with power cable being removed.
Repeat step (d) for ground terminal E1 and green wire (15).
Loosen power cable clamping nut (16) on outside of switch box (5) and pull cable through cable
clamp and out of box.
(2) Installation.
(a)
(b)
(c)
(d)
(e)
(f)
(g)
Feed cable through cable clamping nut (16) and through hole into switch box (5).
Tighten clamping nut (16) on outside of switch box (5) to prevent cable from moving.
Slide terminal of white wire (14) onto load terminal LO (13) and secure with flat washer (12) and
nut (11).
Repeat step (c) for ground terminal E1 and green wire (15).
NOTE
Observe identification tags when installing wires.
Position each of three wires (9) (black, red and blue) against underside of its respective switch
terminal (10). Insert screw (6) up through wire terminal and switch terminal. Install star washer (8)
and nut (7) on screw and tighten against switch terminal. Where an indicator light wire is also
mounted to the switch terminal, the indicator light wire shall be positioned against the underside of the
switch terminal and the power cable wire shall be positioned against the indicator light wire.
Position cover (4) on switch box (5) and secure with 16 screws (l), 16 Iockwashers (2) and 16 flat
washers (3).
Connect power cable to load terminals on generator set. (Refer to paragraph 4-1, a(12).)
e.
Ground Wire Replacement. (See figure 4-13.) Inside the switch box, a wire connects load terminal LO to
AC GROUND terminal E2 located on the side of the switch box below the terminal board.
(1) Removal.
(a)
(b)
(c)
(d)
4-26
Remove 16 screws (1), 16 Iockwashers (2) and 16 flat washers (3) securing cover (4) to switch box
(5) and take cover off switch box.
Remove nut (6) and flat washer (7) from load terminal LO (8) inside switch box (5).
Slide power cable ground (white) wire terminals (9) and switch box ground wire terminal
terminal LO (8).
(10) off load
Remove nut (11 ) and flat washer (12) from AC GROUND terminal E2 (13) inside switch box (5). Slide
ground wire terminal (14) off terminal E2.