2-8. OPERATING PROCEDURES.
WARNING
High voltage is present in this system.
supports equipment using 120/208 V ac.
cover on
unused
feeder/distribution
connectors to avoid electrical shock.
O
Never block circuit
position.
Excessive
PDISE equipment.
CAUTION
DISE and PDISE
Secure connector
center
output
breaker switches in the ON
current will damage DISE and
O
Do not block the feeder/distribution center lids
in the open position.
Rainwater may accumulate
inside feeder/distribution center and damage
components.
NOTE
Refer to proper
technical manuals and FM 20-31 for
operating procedures relating to the particular generator
set used with your DISE and PDISE systems.
a.
Starting Procedures.
WARNING
High voltage is present in this system. DISE and PDISE
supports equipment using 120/208 V ac.
Before turning on
electrical power, alert all users.
Failure to do so may
result in death or severe injury.
(1) Set each DISE and PDISE feeder/distribution center main circuit
breaker to OFF.
(2) Start the generator set.
Refer to TM for proper generator
operating procedures.
(3) Starting with
the feeder/distribution
center
electrically
closest to the generator.
Set the feeder/distribution center main circuit
breaker ON.
(4) Set the circuit breaker for the branch circuits being used to
ON.
(5) Check the current output at the generator for each phase (3-
phase systems only).
If the current draw for any one phase is 10 percent