Table 2-6.
FEEDER/DISTRIBUTION CENTER OUTPUT CONNECTOR LOADS
NOTE
Evenly distribute load across available connectors being
sure total load does not exceed circuit breaker rating.
Balanced
Total
Connector Type
Connector
No. of Connectors kW
(Max Connector Load)
kW Load
Load
a.
b.
c.
d.
M200 and M200 A/P Feeder Centers
(72 kW total output capacity)
100-amp, 8-pin, 3-phase (36 kW)
60-amp, 5-pin, 3-phase (21.6 kW)
20-amp, 3-pin single-phase (2.4 kW)
M100 and M100 A/P Feeder Centers
(36 kW total output capacity)
100-amp, 8-pin, 3-phase (36 kW)
60-amp, 5-pin, e-phase (21.6 kW)
40-amp, 5-pin, 3-phase (14.4 kW)
20-amp, 3-pin, single-phase (2.4 kW)
M40 and M40 A/P Distribution Centers
(14.4 kW total output capacity)
40-amp, 5-pin, 3-phase (14.4 kW)
20-amp, 3-pin, single-phase (2.4 kW)
M60 and M60 A/P Distribution Centers
(7.2 kW total output capacity)
60-amp, 4-pin, single-phase (7.2 kW)
20-amp, 3-pin, single-phase (2.4 kW)
24
18
2.4
36
18
14.4
2.4
14.4
1.2
3
4
1
1
2
2
2
1
12
72*
72*
2.4
36*
36*
28.8
4.8
14.4*
14.4*
7.2
1
7.2*
1.2
6
7.2*
*Requires feeder/distribution centers total output capacity.