TM 9-6150-226-13
CAUTION
If equipment using 3-phase motors is not properly operating, your equipment
is in reverse phase and must be shut down immediately or damage to
equipment may occur. To obtain correct phase, change any two of the
3-phase leads.
(3) Connect the users equipment to the output studs of the universal adapter as follows:
(a) L1 to phase A (black)
(b) L2 to phase B (red)
(c) L3 to phase C (blue)
(d) L0 to neutral (white)
(e) G to ground (green or bare wires)
(4) Connect a 40/60 amp, 5-vvire cable to the input connector of the universal adapter.
(5) Connect the 40/60-amp, 5-wire cable to the proper distribution center output connector.
I. Circuit Cable Loads. Write up and refer to a table of user requirements for your particular field situation.
Each branch circuit cable load must not exceed 2.4 kW or 20 amps(120v x 20 amps -2400 watts). Each
service/feeder cable load must not exceed the kilowatt rating (or amperage rating) of the circuit breaker
supporting that load. Table 2-4 lists the maximum loads for each feeder/distribution center based on output
connectors used. Any combination of output connectors can be used as long as the total load does not exceed
the capacity of the feeder/distribution center and the load is balanced.
2-40