the welder does not contain a military standard connector, use the universal
adapter as described in paragraph 2-7k.
(4) Repeat steps (1) and (2) above for tents #2 and #3.
(5) Connect the pigtail cable to a service/feeder cable of the
desired length selected from Table 1-2.
Connect the service/feeder cable to
the input connector of the M40 or M40 A/P distribution center.
j.
Connection to Generator Set.
o
o
o
o
(1)
Refer to the
WARNING
High voltage is present in this system.
DISE and
PDISE supports equipment using 120/208 V ac.
Do not
connect cables to the generator set with the power on.
Death or severe injury may result.
Ground the generator set.
Death or severe injury may result if
you do not properly ground the generator set.
Connect the ground leads (green) of the pigtail cable to the
ground terminal of the generator set.
Death or severe injury
may result if you do not properly connect the ground leads to
the generator set.
High voltage is present in this system. DISE and PDISE supports
equipment using 120/208 V ac.
The DISE feeder/distribution
centers use ground fault circuit breakers.
The neutral and
ground of some generator sets must be electrically connected
with 6-gage wire
for the ground fault circuit breakers to
function properly.
Failure to electrically connect the ground
and neutral
Physically
proper techn
lugs may result in death or severe injury.
check that the generator set is properly grounded.
cal manuals for grounding procedures.
WARNING
High voltage is present in this system.
DISE and PDISE
supports equipment using 120/208 V ac.
Do not rely on the
color of the wire insulation for phase color-coding.
The
insulation on the wires inside the cable jacket may vary,
depending on the supplier.
Wires will be color-coded to
designate the phases.
Perform a continuity test to verify
correct phase designation in accordance with identified
color.
2-37