TM 9-6150-226-13
(2) Connect the pigtail cable to the generator set as follows:
(a) Black lead (phase A) to L1
(b) Red lead (phase B) to L2
(c) Blue lead (phase C) to L3
(d) White lead (neutral ) to L0
NOTE
For eight-lead cables, twist the four green ground wires
together and connect to ground.
(e) Green (or bare) leads to ground
k.
Universal Adapter.
WARNING
High voltage is present in this system.
DISE and PDISE
supports equipment using 120/208 V ac.
Do not connect
equipment with the power on.
Death or serious injury may
result.
CAUTION
When tightening split lug terminals, use provided insulated
wrench to prevent over tightening.
(1) The universal adapter is designed to connect user electrical
equipment,
without military standard connectors,
to the electrical power
distribution equipment.
(2) The universal adapter (Fig. 2-10) consists of a box with a 5-
pin, 3-phase 40/60 amp input connector and five terminals. The box includes an
insulated wrench for tightening/loosening the terminals.
WARNING
High voltage is present in this system.
DISE and PDISE
supports equipment using 120/208 V ac.
Do not rely on the
color of the wire insulation for phase color-coding.
The
insulation on the wires inside the cable jacket may vary,
depending on the supplier.
Wires will be color-coded to
designate the phases.
Perform a continuity test to verify
correct phase designation
in accordance with identified
color.
2-38