ARMY TM 9-6115-643-10
AIR FORCE TO 35C2-3-445-21
Secure wrench (3) in
d.
Using terminal nut
g.
bracket inside load
terminal board door,
4) loosen terminal
and close door.
nuts (1) on terminals
(2) selected in Step
CAUTION
b.
When using single
e.
Insert ends of load
phase connections,
cables through load
always attempt to
cable entrance box.
balance loads
Insert ends of cables
between terminals
into slots of load
terminal studs (2).
(do not connect
all loads between
one terminal and
f.
Tighten load terminal
LO) . Failure to
nuts (1) .
observe this
caution can result
in damage to
and AM-VM Transfer Switch Selection
AM-VM
RECONNEC-
VOLTAGE
CURRENT
TERMINALS
TRANSFER
TION BOARD
READING
READING
SWITCH
POSITION
(TERMINAL)
POSITION
L1
120
VOLTS
120/208
Ll, L2, L3, LO
L1-LO
L2
120
VOLTS
L2 - LO
3 PHASE.
120
VOLTS
L3
L3 - LO
(SINGLE PHASE
NONE
208
VOLTS
LOADS CAN BE
L1 - L2
NONE
208
VOLTS
L2 - L3
SERVED USING
NONE
208
VOLTS
ANY TERMINAL
L3 - L1
TO LO)
L1
240
VOLTS
L1-LO
240/416
Ll, L2, L3, LO
240
VOLTS
L2
L2 - LO
3 PHASE.
240
VOLTS
L3
L3 - LO
(SINGLE PHASE
416
VOLTS
NONE
LOADS CAN BE
L1 - L2
416
VOLTS
NONE
L2 - L3
SERVED USING
416
VOLTS
NONE
ANY TERMINAL
L3 - Ll
TO LO)