ARMY TM 9-6115-643-10
AIR FORCE TO 35C2-3-445-21
Release MASTER SWITCH
Place AC CIRCUIT
i.
d.
INTERRUPTER switch to
to PRIME AND RUN
position.
CLOSED position.
Ensure voltage and
e.
If operating with an
j.
auxiliary fuel
at rated values.
source, rotate MASTER
Adjust if necessary.
SWITCH to PRIME AND
RUN AUX FUEL
k.
Rotate AM-VM transfer
position.
switch to each phase
NOTE
position while
(PERCENT RATED
Warm up engine
CURRENT) . If more
without load for
than rated load is
(If
five minutes.
indicated in any
required, load can
phase, reduce load.
be applied
immediately) .
1.
Check kilowattmeter
(PERCENT POWER). If
Check COOLANT TEMP
f.
indication is more
[170-200F (77-93C)]
than 100 percent
and OIL PRESSURE [25-
60 psi (172-414 kPa)]
rated load, reduce
load.
indicators for normal
readings.
Turn VOLTAGE and
g.
With any access
potentiometers to
required values for
door open, the
voltage and
noise level of
frequency.
when operating
Press GROUND FAULT
could cause
h.
hearing damage.
CIRCUIT INTERRUPTER
TEST pushbutton.
Hearing protection
Ensure indicator
must be worn when
window is clear.
working near the
Press RESET
while running.
pushbutton and ensure
indicator is red.
m.
Perform all DURING
(D) OPERATION PMCS
requirements in
2-3.
2-23