ARMY TM 9-6115-643-10
AIR FORCE TO 35C2-3-445-21
2-5
PMCS PROCEDURES. - Continued
Table 2-3. Operator Preventive Maintenance Checks and Services
Table 2-2.
Location
Item
Interval
Item to
Procedure
Not Fully Mission
No.
Check/
Capable If:
Service
Generator Set
Exterior
NOTE
continuously at any load from no load up
to and including rated load, However. at
light loads (less than 25% of set rating)
an oily residue (unbumed fuel oil) may
occasionally be noticed In the exhaust
system outlet and around connection
residue is caused by the Inability of the
fuel Injection system to consistently
meter the small amount of fuel required
to operate at these low load levels and
is not a defect In the fuel system The
oily residue could affect engine
performance and create a cosmetic
set. Operation at rated load will bum off
this oily residue The length of time
required at rated load depends on the
also need to be removed and cleaned if
excessive build up occurs This oily
residue can be prevented by increasing
the electrical load on the set
NOTE
If the equipment must be kept in
continuous operation, check and service
only those Items that can be checked
and serviced without disrupting
operations Complete all checks and
services when equipment is shut down
1
Before
Housing
Check door panels, hinges, and latches
Cannot secure
for damage, loose, or corroded Items
door
Inspect air Intake and exhaust grills for
debris
2
Before
Identification
Check to ensure identification plates are
Plates
secure
Change 3
2-9