TABLE 2-2. Malfunction Indicator Panel
Key
Function
1
NO FUEL indicator
Lights when fuel level in fuel tank
is below preset level.
2
COOLANT HIGH TEMP
Lights when engine coolant
indicator
temperature exceeds 220 t 3.5 F
(1040 t 2 F).
3
OVERVOLTAGE indicator
Lights when voltage in 120 volt
generator coil exceeds 153 t 3
volts.
4
OVERSPEED indicator
Lights when engine speed exceeds 2200
t 40 RPM.
5
REVERSE POWER indicator
set exceeds 20 t 3 percent of rated
current.
6
OVER LOAD indicator
Lights when current in any phase
exceeds 110 percent of rated current.
7
GROUND FAULT CIRCUIT
Tests GROUND FAULT CIRCUIT
INTERRUPTER TEST
INTERRUPTER.
pushbutton
8
GROUND FAULT CIRCUIT
Indicates a ground fault condition.
INTERRUPTER indicator
9
GROUND FAULT CIRCUIT
Rests GROUND FAULT CIRCUIT
INTERRUPTER RESET
INTERRUPTER.
pushbutton
10
SHORT CIRCUIT indicator
Lights when generator set output in
any phase exceeds 425 t 25 percent
of rated current.
11
UNDER VOLTAGE indicator
Lights when voltage in 120 volt
generator coil winding drops below
99 t 4 VAC.
12
PUSH TEST RESET LAMPS
Tests and resets fault indicator
switch
lamps.
13
LOW OIL PRESSURE
Lights when engine lubrication
indicator
systems pressure is less than 15 3
psi (103.4 20.7 kPa) during engine
operation.
14
Convenience Receptacle
Circuit breaker trips on when load
Overload Circuit
on convenience receptacle exceeds 10
Breaker (10-amp in-line