ARMY TM 9-6115-643-10
AIR FORCE TO 35C2-3-445-21
b. Push PRESS TO TEST pushbutton on malfunction
2-8 INITIAL ADJUSTMENTS. DAILY CHECKS AND
SELF TEST.
indicator panel. Ensure all indicator lights are lit.
When PRESS TO TEST pushbutton is released, all
2-8.1
Perform all before (B) PMCS, refer to TABLE
lights should go out.
2-3.
c. Press BATTLE SHORT press to test light on the
Initial Adjustments.
2-8.2
control panel assembly. Ensure indicator Iight is lit.
a . Place DEAD CRANK switch in NORMAL position.
When press to test light is released, light should go
out.
b . Push DC CONTROL POWER circuit breaker in.
d. Press AC CIRCUIT INTERRUPTER press to test
Ensure
light on the control panel assembly.
position (50/60 Hz).
indicator light is lit. When press to test Iight is
d . Ensure voftage reconnection terminal board is
released light should go out.
positioned to match voltage requirements. If voltage
reconnection terminal board must be changed,
2-9 OPERATING PROCEDURE.
notify next higher maintenance level.
e .Place AM-VM transfer switch in a position
corresponding to output terminal load connections,
f . Place PARALLEL UNIT switch in UNIT position.
g. Pull out Emergency Stop Switch.
2-8.3 S e l f Test.
is in operation. Improper operation could result
a. Place MASTER SWITCH to PRIME & RUN
in personal injury or death.
position.
Change 1