TM 9-6150-226-13
4-15 CONNECTOR ASSEMBLY. (cont)
Tag and disconnect receptacle/
plug wiring from circuit breaker
and bus bar terminals
Remove screw (1) securing
receptacle/plug and gasket (2)
and remove connector,
2. INSTALL CONNECTOR.
a. Install receptacle/plug and
gasket (2) in mounting hole
and secure with screw (1).
b. Connect receptacle/plug wiring
and remove tags. Remove tags
and torque terminal lugs in
accordance with Table G-1.
WARNING
High voltage is present
in this system. DISE
and PDISE supports equip-
ment using 120/208 V ac.
Do not attempt continuity
check with the power on.
Death or severe injury may
result.
TEST
PERFORM CONTINUITY TEST
Refer to Table 4-4 and perform continuity test on the feeder/distribution center.
FOLLOW-ON MAINTENANCE: Install cover panel, circuit breaker assembly, and
lanyards (para 4-14).
4-44