ARMY TM 9-6115-673-13&P
AIR FORCE TO 35C2-3-512-1
Table 4-22. Air Intake Preheaters Do
Not Operate
Troubleshooting
Air intake heaters
do not operate
OK
Not OK
connector (P2) is connected to
control panel receptacle (J2)
Inspect for defective NATO
OK
Not OK
slave receptacle (SR1)
harness connector (P2)
Replace defective NATO
Test for defective
Not OK
OK
slave receptacle (SR1)
START/PREHEAT/OFF/START switch
Replace defective START-
Test for defective air intake
PREHEAT/PREHEAT/0FF/START
heaters (HTR1 or HTR2).
switch (S2)
Disconnect two wires and
Not OK
terminals. If open - one or
both heaters are bad
or jumper is missing.
Replace air intake heater(s)
(HTR1 or HTR2),