4-31. GROUND FAULT CIRCUIT INTERRUPTER MAINTENANCE (60 HZ, MEP 831A ONLY)
- cont.
C. INSTALLATION.
1.
Mate ground fault circuit interrupter (1, Figure 4-22) to back of control box. Secure using screws (2),
washers (3), and nuts (4).
2.
Connect ground fault circuit interrupter (1) electrical wiring to terminal board TB4. Install cover onto TB4
(Para. 4-25).
3.
Install battery and tray (Para. 4-45). Install convenience receptacle (Para. 4-30).
4.
Close main access cover and lock in place using latches.