TM 5-6115-627-14&P
Figure 5-5. Power Cable Repair.
b. Installation.
(1) Solder replacement contact(s) (11) on wire(s) (12).
(2) Align and insert contact(s) (11) into spacer (9) until contacts are fully seated.
(3) Align insert (10) with plug shell (8) so key on insert matches keyway in plug shell and push insert into
shell until it seats.
(4) Align contacts (11) with corresponding holes in insert (10) and slide contacts into insert until spacer (9) is
flush against insert.
(5) Slide housing (2) up against plug shell (8) and secure with three screws (6) and three washers (7).
(6) Slide collar (4) and packing gland (3) up cable (5) into housing (2).
5-6
(7) Tighten cable grip nut (1) against housing (2).
(8) Test cable for continuity (paragraph 4-27).