(1) Removal.
(a)
(b)
(c)
(d)
(e)
Remove 24 screws (1, figure 5-7), 24 Iockwashers (2), and 24 flat washers (3) securing access cover
(4) to switch box (5) and remove cover.
Disconnect connector cable assembly ground wire (6) from ground stud E1 (7) by removing nut (8),
Iockwasher (9), flat washer (10), and three electrical leads (11).
Disconnect each of three connector cable assembly wires (12) from terminals of associated switch
(13) by removing one nut (14) and one Iockwasher (15).
Disconnect connector cable assembly neutral wire (16) from load terminal L0 (17) on insulator TB1
(18) by removing nut (19), Iockwasher (20) and flat washer (21).
Remove four screws (22) and four self-locking nuts (23) securing connector flange (24) to switch box
(5). Carefully remove connector and associated wiring from switch box.
(2) Installation.
(a)
(b)
(c)
(d)
(e)
Feed connector cable assembly wires through mounting hole in switch box (5).
Position connector body in mounting hole and secure with four screws (22) and four nuts (23). Use
screw in lower right-hand corner of flange (24) to secure connector cap retaining chain (25).
NOTE
When reconnecting wires, refer to figure 4-14
Fasten each of three connector cable assembly wires (12) to terminals of associated switch (13) with
one nut (14) and one Iockwasher (15).
Fasten cable assembly ground wire (6) to ground stud E1 (7) with nut (8), Iockwasher (9) and flat
washer (10). Make sure electrical leads (11) are reinstalled and positioned as shown in figure 5-7.
Fasten cable assembly neutral wire (16) to load terminal L0 (17) with flat washer (21), Iockwasher
(f)
(20) and nut (19).
Position access cover (4) on switch box (5) and secure with 24 screws (1), 24 Iockwashers (2), and
24 flat washers (3).
c.
Load Terminal Replacement.
(See figure 5-8.) The switch box load terminals provide electromechanical
connection points between the system or equipment being powered and the power plant. In addition to the four
output terminals, the switch box utilizes a fifth load terminal as AC GROUND.
WARNING
To avoid risk of injury or death by electrocution, do not remove switch box access cover
while either power unit is still connected to switch box.