TM 9-6150-228-13&P
Figure 4-12. MS Connectors.
REMOVAL
NOTE
The 60-amp and 100- amp connectors differ only in number of wires and relative sizes.
There are fourteen connectors on the power distribution panel and this procedure is typical for
all.
a. Loosen socket-head screw on each output terminal (1, Figure 413) of corresponding circuit breaker (2).
b. Tag and remove three connection wires (3).
c. Remove screws (4) securing neutral and ground wires from connector to associated bus bars (5) and remove wires
(6).
4-37