TM 9-6115-730-10
0012 00
PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS), INCLUDING LUBRICATION
INSTRUCTIONS Continued
Table 1. Preventive Maintenance Checks and Services Continued.
LOCATION/
NOT FULLY
ITEM
ITEM TO
MISSION
NO.
INTERVAL
CHECK/SERVICE
PROCEDURE
CAPABLE IF:
14
Before
Cooling Fan
Check fan for damage or looseness.
Cooling fan is
damaged or loose.
15
Before
Fan Belts
Inspect belts to ensure that they are not
Broken, missing, or
missing. Inspect for cracks, fraying and
loose belt(s).
looseness.
16
Before
Overflow Bottle
Check over-flow bottle for leaks or missing
Class III leaks or
parts.
overflow bottle
missing.
Check coolant level above COLD line in
Coolant level is below
COLD line.
17
Before
Exhaust System
corrosion, damaged, or missing parts.
system have missing
parts.
Check exhaust system for restrictions and
Restricted exhaust
proper venting to atmosphere.
18
Before
Air Cleaner
Inspect air cleaner assembly and piping for
Clogged element is
Assembly
loose or damaged connections.
indicated (red),
piping and
Check restriction indicator for clogged
connections are
loose, restriction
indicator broken or
missing.
19
Before
Battery Cables
__________
WARNING
set electrical components even with
generator set shut down. Avoid
shorting any positive with
ground/negative. Failure to comply
can cause injury to personnel and
damage to equipment.
Inspect cables and connectors for corrosion,
Cables are loose,
loose, damaged or missing parts.
damaged or
missing.
Batteries fail to start
generator.
0012 00-7