TM 9-6115-730-10
200 kW TACTICAL QUIET GENERATOR SET
0012 00
PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS), INCLUDING LUBRICATION
INSTRUCTIONS Continued
Table 1. Preventive Maintenance Checks and Services Continued.
LOCATION/
NOT FULLY
ITEM
ITEM TO
MISSION
NO.
INTERVAL
CHECK/SERVICE
PROCEDURE
CAPABLE IF:
24
Before
Generator Set
GSC indicator lights
Touch LAMP TEST on keypad and check
Control
and display
that all eight indicator lights on GSC and
segments do not
upper and lower display segments light.
light.
25
Before
Alarm Module
Alarm Module lights
Press LAMP TEST and check that alarm
do not light and
indicators light and alarm sounds.
alarm does not
sound.
26
Before
Parallel Cable
Paralleling cable
missing or cable and
inspect parallel cable for damage.
connectors are
damaged.
__________
27
Before
Ground Rod Cable
WARNING
and Connection
High voltage is produced when the
generator set is in operation. Never
it is properly grounded. Failure to
comply can cause injury or death to
personnel.
Any missing or
Inspect ground rod and cable for loose
damaged parts.
connections, breaks, damage and
corrosion.
PU-809A TRAILER
INSTALLATION
If generator set is trailer-mounted (PU-
28
Before
Identification plates
809A), check to ensure identification
plates on trailer are secure.
29
Before
Fire Extinguisher
Fire extinguishers are
Verify that two fire extinguishers mounted
not present or not
to trailer brackets and fully charged.
certified. Needle is
Check that fire extinguisher needle (if
not in green zone.
applicable) is in green zone.
Check fire extinguisher seal. If seal is
broken or missing, replace fire
extinguisher.
Visually inspect bracket for obvious
damage.