TM 9-6115-730-10
0006 00
OPERATION UNDER USUAL CONDITIONS Continued
INITIAL ADJUSTMENTS BEFORE USE AND SELF-TEST
Initial Adjustments
1.
Open right rear side access door and ensure voltage Reconnection Board (WP 0005, Table 9) is set to match voltage
requirements of load (WP 0006, Table 1). If voltage Reconnection Board must be changed and GSC and DVR must be
programmed to give required output, notify maintenance.
2.
If using external fuel supply, connect auxiliary fuel supply hose per WP 0006 00-6.
3.
Open left rear generator housing door and set DEAD CRANK SWITCH to NORMAL (WP 0005 00-12).
4.
On Electronic Modular Control Panel (EMCP) momentarily set AC CIRCUIT INTERRUPTER to OPEN (down).
NOTE
FREQUENCY and VOLTAGE potentiometers should be adjusted in the center position. The position is
not marked on the control panel. To center each potentiometer, the operator must turn the potentiometer as
far as it will go in one direction and then rotate it five full turns in the opposite direction.
5.
Adjust FREQUENCY potentiometer to center position. Rotate potentiometer clockwise until it stops. Then rotate it five
full turns counterclockwise.
6.
Adjust VOLTAGE potentiometer to center position. Rotate potentiometer clockwise until it stops. Then rotate it five
full turns counterclockwise.
7.
Set PARALLEL/UNIT switch to UNIT.
8.
Pull out PUSH TO STOP EMERGENCY STOP switch.
9.
Self-Test
1.
2.
Verify that there is fuel in the TQG fuel tank. A full fuel tank will provide at a minimum eight hours of operation.
3.
On Generator Set Control (GSC), touch LAMP TEST on keypad. Ensure that all indicator lights on GSC light
4.
On Alarm Module, press LAMP TEST on panel. Ensure that alarm indicators light (WP 0005 00-9). Indicator lights
turn on and alarm module horn sounds.
5.
Press AC CIRCUIT INTERRUPTER press-to- test green indicator on the EMCP. Ensure indicator lights up. When
6.
If equipped with winterization kit, press HEATER press-to-test lamp on FUEL FIRED HEATER CONTROL panel.
END OF TASK