TM 9-6115-730-10
0005 00
DESCRIPTION AND USE OF OPERATOR CONTROLS AND INDICATORS Continued
GENERATOR SET CONTROL
Table 2 describes the EMCP GSC indicator lights and light emitting diode (LED) displays.
Table 2. Generator Set Control Controls and Indicators.
CONTROL OR
KEY
INDICATOR
FUNCTION
1
LOW OIL PRESSURE
Red indicator flashes when oil pressure drops below the programmed low oil pressure
shutdown indicator
setpoints. Engine shuts down and does not run until fault is corrected.
2
EMERGENCY STOP
Red indicator flashes when PUSH TO STOP EMERGENCY STOP pushbutton is
shutdown indicator
pressed on control panel. Engine shuts down and does not start until pushbutton is
pulled out and ENGINE CONTROL switch is set to OFF/RESET and back to
AUTO or MANUAL START. PUSH TO STOP EMERGENCY STOP pushbutton
switch can be reset by turning knob to right or pulling out.
3
HIGH WATER TEMP
Red indicator flashes when engine coolant temperature rises above programmed
shutdown indicator
setpoint for high coolant temperature shutdown. Engine shuts down and does not
start until fault is corrected.