TM 9-6115-730-10
200 kW TACTICAL QUIET GENERATOR SET
0005 00
DESCRIPTION AND USE OF OPERATOR CONTROLS AND INDICATORS Continued
GENERATOR SET CONTROL Continued
Table 2. Generator Set Control Controls and Indicators Continued.
CONTROL OR
KEY
INDICATOR
FUNCTION
Additional functions will scroll if key held for more than 5 seconds:
Total real power (kW)
Real power phase A (kW)
Real power phase B (kW)
Real power phase C (kW)
Total apparent power (kVA)
Total reactive power (kVA)
Percentage of rated power (%kW)
Power factor (average) (PF)
Power factor phase A
Power factor phase B
Power factor phase C
Total energy output (kWh)
Total reactive energy output (kVARHr)
14
AC METER
Selects phase of generator output that is shown on upper display. Pressing this key
allows operator to check voltage, current, and frequency of each phase one at a
time. Options are as follows:
Voltage (average), frequency, current (total)
Voltage (line to line), frequency, current (line) for any one phase
Voltage (line to line) for all three phases at once
Current (line) for all three phases at once
Voltage (line to neutral) for all three phases at once
15
ENGINE METER
Stops scrolling of engine condition data shown on lower display. Pointer flashes to
indicate that scrolling is stopped. Pressing key again resumes scrolling. Sequence
of reported data is as follows:
Fuel filter run hours
Oil filter run hours
Battery voltage
Engine run hours
Engine rpm
Engine oil pressure
Engine coolant temperature
16
LAMP TEST
Performs lamp test on GSC. Eight fault indicators are on continuously and all
segments of upper display and lower display are on.
17
ALARM CODES
If FAULT ALARM light is flashing, pressing this key displays diagnostic code
(WP 0009 00) in
upper display. Pressing key again resumes display of
generator
output information. If FAULT ALARM light is off, this key has no function.
18
EXIT
Service Mode. FOR MAINTENANCE PERSONNEL USE ONLY.
19
SERVICE MODE
Service Mode. FOR MAINTENANCE PERSONNEL USE ONLY.
0005 00-8