TM 9-6115-730-10
200 kW TACTICAL QUIET GENERATOR SET
0005 00
DESCRIPTION AND USE OF OPERATOR CONTROLS AND INDICATORS Continued
ELECTRONIC MODULAR CONTROL PANEL Continued
Table 1. Tactical Quiet Generator Electronic Modular Control Panel Controls and Indicators Continued.
CONTROL OR
KEY
INDICATOR
FUNCTION
11
AC CIRCUIT
Three-position toggle switch.
INTERRUPTER switch
CLOSED
Up momentary toggle activates circuits to close load contactor. Connects TQG
to load.
Press-to-test green indicator is lit when load contactor is closed.
Normal
Toggle switch spring loaded to return to this position.
OPEN
Down momentary toggle activates circuits to open load contactor. Disconnects
TQG from load.
Press-to-test green indicator is off when load contactor is open.
12
Press-to-test green indicator
Indicator lights when AC CIRCUIT INTERRUPTER switch is set to CLOSED.
Indicator off when AC CIRCUIT INTERRUPTER switch is set to OPEN.
13
PUSH TO STOP
Press for emergency stop of TQG. Switch pulled out for normal operations.
EMERGENCY STOP
Switch can be reset by turning knob to right and pulling out.
pushbutton switch
14
BATTLE SHORT switch
Two-position toggle switch. Hinged red safety cover must be raised to set to
ON.
ON
Disables all safety or protective devices except short circuit and overspeed.
Disables starting of engine. Yellow LED on GSC is lit.
OFF
Normal operation of generator set. Lowering red cover returns switch to OFF.
15
ENGINE CONTROL switch
Four-position rotary switch.
OFF/RESET
Engine shuts down and fault indicators and overload/short circuit module are
reset, except in emergency stop while EMERGENCY STOP pushbutton is in.
AUTO
Allows remote start/stop control.
MANUAL START
Starts and runs generator set diesel engine.
COOL DOWN/STOP
Shuts engine down after 5-minute cool down period has passed.
16
AUX FUEL switch
Two-position switch controls auxiliary fuel pump.
ON
Turns on auxiliary fuel pump to supply fuel from external fuel supply.
OFF
Only allows fuel to be consumed from generator set fuel tank.