ARMY TM 9-6115-670-14&P
5-101
m. Lift APU (9) off resilient mounts (6) or vibration isolator mount (18), and set on surface where
there is support for generator brackets (8) and engine brackets (7).
n. (SICPS) use lifting device to set generator brackets (8) and engine brackets (7) on resilient
mounts (6).
o. (JTACS and WIN-T) Align spacers (19) over installation holes on isolator mount (18). Using
lifting device, place and align APU over spacers. Slowly lower unit to frame and carefully
adjust APU over spacers as needed.
p. (JTACS and WIN-T) Secure alternator to isolator mount (18) with four hex-head socket screws
(20).
q. (JTACS and WIN-T) secure generator (10) brackets to vibration isolator mount (18) with two
bolts, flat washers and lock nuts; and secure engine brackets (9) to vibration isolator mount
(20) with four allen screws and lock washers.
r. (SICPS) Secure generator brackets (8) and engine brackets (7) on resilient mounts (6).
s. Remove lifting device from lifting eyes (5 and 6).
t. Install 24 VDC to starter and reconnect AC output.
u. Install fuel pump bracket (1, Figure 4-18) to generator mount (8) (SICPS) with one screw, flat
and lock washer (3), or to isolator mount (JTACS and WIN-T) with one bolt, flat and lock
washer.
WARNINGS
DO NOT stand or sit on the generator as it is being
hoisted, lowered, or transported.
DO NOT lift the generator over personnel.
When using lift ring, ensure that a closed ring with
safety latch is used. NO OPEN HOOKS are to be used
when lifting APU.
Lift ring must have a swivel attached to prevent
equipment from swinging.
Hard hats must be worn when APU is removed by
overhead lift ring.
CAUTION
Avoid blocking unit using the oil pan located beneath
unit. Ensure unit is blocked using alternator space in
front of oil pan and alternator to avoid damage to
equipment.
NOTE
Once APU is correctly aligned over spacers, APU can
be secured to isolator mount. Hardware is installed
beneath isolator mount.