ARMY TM 9-6115-670-14&P
5-103
(3)
Install pull handle brackets (22 and 24) and pull handle (23) and secure with four screws,
washers, and lock washers (21).
(4)
Install vibration isolator mount assembly (18) to frame with ten hex-head bolts (30), flat
and lock washers.
c. To repair APU Vibration Isolator Mount Assembly (18), refer to Figure 5-24 (sheet 6) and
proceed as follows:
(1)
Remove 20 countersunk screws (37) securing top isolator mount plate (36) to isolator
mount assembly (18).
(2)
Remove two screws and flat washers (41) securing coupling plate (40) to top isolator
mount plate (36).
(3)
Remove two screws (37) securing coil (38) to bottom plate (39).
(4)
Install coil (38) to bottom plate (39) with two screws (37).
(5)
Install plate (40) to top isolator mount plate (36) with two screws and flat washers (41).
(6)
Install top isolator mount plate (36) to isolator mount assembly (18) with 20 screws (37).
NOTE
There are a total of 40 screws securing both top and
bottom isolator mount plates to isolator mount
assembly.
NOTE
Each coil is attached to bottom plate with two screws.
Remove screws as necessary for each coil being
replaced.