ARMY TM 9-6115-645-10
AIR FORCE TO 35C2-3-444-11
MARINE CORPS TM 09244A/09245A-10/1
With any access
door open, the
noise level of
this generator set
when operating
could cause
hearing damage.
Hearing protection
must be worn when
working near the
generator set
while running.
m.
Perform all DURING
(D) OPERATION PMCS
requirements in
accordance with TABLE
2-3.
2-9.2 Stopping Procedure.
a.
Place AC CIRCUIT
INTERRUPTER switch in
OPEN position.
b.
Allow generator set
to operate five
minutes with no load
applied.
c.
Place MASTER SWITCH
in OFF position.
d.
Perform all AFTER (A)
OPERATION PMCS
requirements in
accordance with TABLE
2-3.
e.
Place DEAD CRANK
switch in OFF
position.
2-10
2-10.1
method
PARALLEL UNIT OPERATION
(LOAD SHARING).
CAUTION
Ensure generator
sets are the same
size and mode
before attempting
parallel
operation.
General. The following
of parallel operation
will be used to share the load
between two generator sets.
Refer to FIGURE 2-1 for location
of operator controls and
indicators mentioned below and
FIGURE 2-5 for proper
paralleling configuration.
2-10.2 Pre-Operation.
Prior to making
any connections
for parallel
operation, ensure
that there is no
input to the load
and that the
generator sets are
shut down.
Failure to observe
this warning can
result in injury
or death by
electrocution.
a.
Ensure that load
requirement is equal
or below the
combined rated
capacity of the two
generator sets.
2-24