ARMY TM 9-6115-645-10
AIR FORCE TO 35C2-3-444-11
MARINE CORPS TM 09244A/09245A-10/1
Never attempt to
start the
generator set if
it is not
properly
grounded.
Failure to
observe this
warning could
result in
serious injury
or death by
electrocution.
b.
Determine voltage
requirements of load
and position voltage
reconnection
terminal boards of
the two generator
sets to the required
voltage connection.
Ensure FREQUENCY
SELECT switch (MEP-
806A) for both
generators are
positioned for the
same load
requirements.
c.
Identify one
generator set as No.
1 and the other as
No. 2.
d.
Remove paralleling
cable from storage
box located inside
battery compartment
access door.
e.
Connect the
paralleling cable
between the two
generator sets.
Connect the
generator sets to
the load observing
the proper phase
polarity.
CAUTION
Do not close the
AC CIRCUIT
INTERRUPTER
switch on either
of the generator
sets, nor close
the load
contactor at
load until
specifically
directed to do
SO.
Closing any
of these devices
at any other
time may
severely damage
one or both of
the generator
sets.
2-10.3 Operation.
a.
Start each generator
set, refer to
paragraph 2-9.1.
b.
Rotate both VOLTAGE
adjust potentio-
meters to obtain the
same voltage
indication on each
set.
2-26