ARMY TM 9-6115-645-10
AIR FORCE TO 35C2-3-444-11
MARINE CORPS TM 09244A/09245A-10/1
j.
Rotate the VOLTAGE
adjust potentio-
meter of generator
set No. 1 until
ammeter (PERCENT
RATED CURRENT) reads
approximately O".
k.
Close the load
contactor at the
load.
NOTE
If the REVERSE
POWER indicator
of either
generator set
lights, and the
AC Circuit
Interrupter
relay opens,
open the load
contactor at
load and de-
synchronize the
generator sets.
(Repeat the
necessary steps
d through k
above.)
l.
Compare ammeter
(PERCENT RATED
CURRENT) readings of
both generator sets.
If readings are not
within 10 percent,
notify next higher
level of
maintenance.
m.
Compare kilowatt-
meter (PERCENT
POWER) readings of
both generator sets.
If readings are not
within 10 percent,
notify next higher
level of
maintenance.
2-10.4 Removal from Parallel
Operation.
If necessary to
move a generator
set which has
been operating
in parallel with
another genera-
tor set, shut
down remaining
generator set
connected to the
load, prior to
removing load
cables or
ground.
Failure
to observe this
warning can
result in injury
or death by
electrocution.
Prior to removal
of generator set
from parallel
operation, make
sure load does
not exceed full
load rating of
generator set
remaining on the
line.
Failure
to observe this
caution can
result in damage
to generator
set.
a.
Position AC CIRCUIT
INTERRUPTER switch
to OPEN until
indicator goes out.
b.
Return UNIT-PARALLEL
switch to UNIT
position.
2-28