2-8 INITIAL ADJUSTMENTS, DAILY CHECKS
AND SELF TEST.
2-8.1 Perform all before (B) PMCS, refer to Table 2-3.
2-8.2 Initial Adjustments.
a.
b.
c.
d.
e.
f.
g.
Place DEAD CRANK switch in NORMAL posi-
tion.
Push DC CONTROL POWER circuit breaker in.
Place FREQUENCY SELECT switch to required
position (MEP-806A).
Ensure voltage reconnection terminal board is posi-
tioned to match voltage requirements. If voltage
reconnection terminal board must be changed,
notify next higher maintenance level.
Place AM-VIM transfer switch in a position corre-
sponding to output terminal load connections, refer
to Table 2-4.
Place PARALLEL UNIT switch in UNIT position.
Pull out EMERGENCY STOP switch.
ARMY TM 9-6115-645-10
AIR FORCE TO 35C2-3444-11
MARINE CORPS TM 09244A/09245A-10/1
2-8.3 Self Test.
a
b.
c.
d.
Place MASTER SWITCH to PRIME AND RUN
position.
Push PRESS TO TEST pushbutton on malfunction
indicator panel. Ensure all indicator lights are lit.
When PRESS TO TEST pushbutton is released, all
lights should go out.
Press BATTLE SHORT press to test light on the
control panel assembly. Ensure indicator light is lit.
When press to test light is released, light should go
out.
Press AC CIRCUIT INTERRUPTER press to test
light on the control panel assembly. Ensure indica-
tor light is lit. When press to test light is released
light should go out.
Change 1 2-21