d.
Using terminal nut
wrench (3, FIGURE 2-
4) loosen terminal
nuts (1) on terminals
(2) selected in Step
b.
e.
Insert ends of load
cables through load
cable entrance box.
Insert ends of cables
into slots of load
terminal studs (2).
f.
Tighten load terminal
nuts (1).
ARMY TM 9-6115-645-10
AIR FORCE TO 35C2-3-444-11
MARINE CORPS TM 09244A/09245A-10/1
g.
Secure wrench (3) in
bracket inside load
terminal board door,
and close door.
CAUTION
When using single
phase connections,
always attempt to
balance loads
between terminals
(do not connect
all loads between
one terminal and
LO).
Failure to
observe this
caution can result
in damage to
generator set.
TABLE 2-4.
Load Terminal, AC Reconnection Board
and AM-VM Transfer Switch Selection
RECONNEC-
AM-VM
TION BOARD
TERMINALS
TRANSFER
VOLTAGE
CURRENT
POSITION
SWITCH
READING
READING
POSITION
(TERMINAL)
120/208
L1, L2, L3, LO
L1 -LO
120 VOLTS
L1
3 PHASE.
L2 -LO
120 VOLTS
L2
(SINGLE PHASE
L3-LO
120 VOLTS
L3
LOADS CAN BE
L1-L2
208 VOLTS
NONE
SERVED USING
L2-L3
208 VOLTS
NONE
ANY TERMINAL
L3-L1
208 VOLTS
NONE
TO LO)
240/416
L1, L2, L3, LO
L1-LO
240 VOLTS
L1
3 PHASE.
L2-LO
240 VOLTS
L2
(SINGLE PHASE
L3-LO
240 VOLTS
L3
LOADS CAN BE
L1-L2
416 VOLTS
NONE
SERVED USING
L2-L3
416 VOLTS
NONE
ANY TERMINAL
L3-L1
416 VOLTS
NONE
TO LO)
2-19