2-47-4 Installation.
a.
Install GROUND FAULT ClRCUIT INTERRUPTER (23, FIGURE 2-14) in malfunction indicator panel (27) with
screws (21) and nuts (22).
b.
Connect electrical leads to TB4 and K5, CONVENIENCE RECEPTACLE (20), and remove tags.
c.
Install control box top panel, paragraph 2-15-4.
d.
Connect negative battery cable. Close battery access door.
2-48 MALFUNCTION INDICATOR PANEL
2-48-1
a.
b.
2-48-2
a.
b.
2-48-3
a.
b.
c.
d.
e.
f.
g.
2-48-4
a.
Inspection.
Shut down generator set.
Inspect malfunction indicator panel for broken indicator lights, cracked housing, corrosion, and other damage.
Testing.
Depress TEST/RESET button and check that all indicators are lit.
Replace malfunction indicator panel if one or more indicators do not light.
Removal.
Shut off generator set.
Open battery access door and disconnect negative battery cable.
Release control panel by turning two fasteners and lower control panel slowly.
Remove GROUND FAULT CIRCUIT INTERRUPTER, paragraph 2-47-3 (Do not disconnect electrical leads).
Disconnect multi-pin connector at rear of malfunction indicator panel (27, FIGURE 2-14).
Remove bolts (24), washers (25), and nuts (26).
Remove malfunction indicator panel (27) from control panel.
Installation.
Install malfunction indicator panel (27, FlGURE 2-14) in control panel with bolts (24), washers (25), and nuts
(26).
b.
Install multi-pin connector at rear of panel.
c.
Install GROUND FAULT CIRCUIT INTERRUPTER paragraph 2-47-4.
d.
Raise and secure control panel.
e.
Connect negative battery cable. Close battery access door.
2-49 BATTERY CHARGER FUSE
2-49-1
Removal.
a.
Shut down generator set.
Change 1 2 - 8 3