ARMY TM 9-6115-644-24
AIR FORCE TO 35C2-3-446-12
MARINE CORPS TM 09249A/09246A-24/2
g.
2-46-3
a.
b.
c.
d.
e.
f.
g.
2-46-4
a.
b.
c.
d.
e.
Install control box top panel, paragraph 2-15-4.
Removal.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Remove control box top panel, paragraph 2-15-1.
Remove screws (15, FIGURE 2-14) and nuts (16).
Remove CONVENIENCE RECEPTACLE cover (17).
Remove machine screws (18), nuts (19), and CONVENIENCE RECEPTACLE (20).
Tag and disconnect CONVENIENCE RECEPTACLE (20) electrical leads.
Connect electrical leads to CONVENIENCE RECEPTACLE (20, FIGURE 2-14) and remove tags.
Install CONVENIENCE RECEPTACLE (20) into panel cutout with machine screws(18) and nuts (19).
Install CONVENIENCE RECEPTACLE cover (17) with screws (15) and nuts (16).
Install control box top panel, paragraph 2-15-4.
Connect negative battery cable, Close battery access door.
Installation.
2-47 GROUND FAULT CIRCUIT INTERRUPTER.
2-47-1
a.
b.
2-47-2
a.
b.
c.
d.
2-47-3
a.
b.
c.
d.
e.
2-82
Inspection.
Shut down generator set.
Inspect GROUND FAULT CIRCUIT INTERRUPTER for cracks, corrosion, frayed wires, and other damage.
Testing.
Start and operate generator set at rated voltage and frequency.
Set multimeter for AC volts, press TEST button and check for zero voltage at the CONVENIENCE
RECEPTACLE.
Press RESET button and use multimeter to check for 120 VAC at the CONVENIENCE RECEPTACLE.
Replace GROUND FAULT CIRCUIT INTERRUPTER if indications are other than above.
Removal.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Remove control box top panel, paragraph 2-15-1.
Tag and disconnect GROUND FAULT CIRCUIT INTERRUPTER (23, FIGURE 2-14) electrical leads from TB4
and K5, and CONVENIENCE RECEPTACLE (20).
Remove screws (21) and nuts (22).