Open battery access door and disconnect negative battery cable.
Relase control panel by turning two fasteners and lower control panel slowly.
Remove cap (28, FIGURE 2-14) and fuse (29) from fuse holder (32).
Tag and unsolder electrical leads from fuse holder (32).
Remove nut (30), lockwasher (31), and fuse holder (32).
Inspection.
Shut down generator set.
Inspect for blown fuse.
Inspect fuse, fuse holder, and cap for cracks, corrosion, and obvious damage.
Replace defective parts.
Installation.
Install fuse holder (32, FlGURE 2-14) and secure with lockwasher (31) and nut (38).
Solder electrical leads to fuse holder (32) and remove tags.
Install fuse (29) and cap (28).
Raise and secure control panel.
Connect negative battery cable. Close battery access door.
2-50
DC CONTROL POWER CIRCUIT BREAKER.
2-50-1
a.
b.
2-50-2
a.
b.
c.
d.
e.
f.
g.
h.
i.
j
2-84
Inspection.
Shut down generator set.
Inspect circuit breaker for loose connections and mounting, cracked housing, and other damage.
Testing.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Release control panel by turning two fasteners and lower control panel slowly.
Tag and disconnect DC CONTROL POWER circuit breaker (35, FIGURE 2-14) electrical leads.
Place circuit breaker in OPEN position.
Set multimeter for ohms and connect across circuit breaker terminals. Multimeter should indicate open circuit.
Place circuit breaker in the CLOSED position. Multimeter should indicate continuity.
Replace circuit breaker if indications are not as above.
Connect electrical leads to circuit breaker (35) and remove tags.
Raise and secure control panel.