ARMY TM 9-6115-644-24
AIR FORCE TO 35C2-3-446-12
MARINE CORPS TM 09249A/09246A-24/2
Turn LOAD SHARING ADJUST rheostat to full counter clockwise position. Multimeter reading should be be-
tween 4500 and 5500 ohms.
Turn LOAD SHARING ADJUST rheostat to full clockwise position. Multimeter reading should be approximately
O ohms.
Replace LOAD SHARING ADJUST rheostat if multimeter readings are other than above.
If readings are within tolerance, return rheostat to reading recorded in step f.
Connect electrical wires as tagged.
Install control box top panel, paragraph 2-15-4.
Connect negative battery cable and close battery access door.
Removal.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Remove control box top panel, paragraph 2-15-1.
Tag and disconnect LOAD SHARING ADJUST rheostat (7, FIGURE 2-14) electrical leads.
Remove nuts (4) and (5), Iockwasher (6), and rheostat (7).
Install LOAD SHARING ADJUST rheostat (7, FIGURE 2-14) in mounting bracket.
Install Iockwasher (6) and nuts (5) and (4).
Connect electrical leads and remove tags.
Install control box top panel, paragraph 2-15-4.
Connect negative battery cable. Close battery access door.
Installation.
2-44
OVERSPEED RESET SWITCH,
2-44-1
a.
b.
2-44-2
a.
b.
c.
d.
e.
f.
Inspection.
Shut down generator set.
Inspect switch for loose connections and mounting, and other damage.
Testing.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Remove control box top panel, paragraph 2-15-1.
Tag and disconnect OVERSPEED RESET switch (10, FIGURE 2-14) electrical leads.
Set multimeter for ohms and connect across switch terminals. Multimeter should indicate continuity,
Position and hold switch in the up position. Multimeter should indicate open circuit.