ARMY TM 9-6115-644-24
AIR FORCE TO 35C2-3-446-12
MARINE CORPS TM 09249A/09246A-24/2
f.
2-40-3
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
2-40-4
a.
b.
c.
d.
e.
Remove PANEL LIGHTS switch (40) from control panel and tab washer (41) from switch stem.
Testing.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Release control panel by turning two fasteners and lower control panel slowly.
Tag and disconnect PANEL LIGHTS switch (40, FIGURE 2-13) electrical leads.
Set multimeter for ohms and connect across switch terminals.
Place switch in ON position. Multimeter should indicate continuity.
Place switch in OFF position. Multimeter should indicate open circuit.
Replace PANEL LIGHTS switch if readings are not as above.
Connect electrical leads to switch (40) and remove tags.
Raise and secure control panel.
Connect negative battery cable and close battery access door.
lnstallation.
Install tab washer (41, FIGURE 2-13) and insert PANEL LIGHTS switch (40) into control panel.
Install washer (39) and nut (36).
Install electrical leads and remove tags.
Raise and secure control panel.
Connect negative battery cable. Close battery access door.
2-41 EMERGENCY STOP SWITCH.
2-41-1
a.
b.
2-41-2
a.
b.
c.
d.
e.
f.
2-41-3
2-76
Inspection..
Shut down generator set.
Inspect switch for loose connections and mounting, and other damage.
Removal.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Release control panel by turning two fasteners and lower control panel slowly.
Tag and disconnect EMERGENCY STOP switch (44, FIGURE 2-13) electrical leads.
Remove knob (42) and nut (43).
Remove EMERGENCY STOP switch (44) from control panel.
Testing.