ARMY TM 9-6115-643-24
AIR FORCE TO 35C2-3-445-22
2.95.3. Repair.
a.
b.
c.
d.
e.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Open applicable access doors.
Replace damaged terminals and securing hardware.
Connect negative battery cable and close all access doors.
2.96. CURRENT TRANSFORMER.
2.96.1 lnspection.
a. Shut down generator set.
b. Open output box access door.
c. Inspect current transformer (7, FIGURE 2-29) for security, cracked housing, broken or stripped terminals, and
loose or missing hardware.
d. Close output box access door.
2.96.2. Testing.
a .
b.
c .
d .
e.
f.
g.
h.
i.
2.97.
a.
b .
c.
d.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Open output box access door.
Tag and disconnect electrical leads from current transformer (7, FIGURE 2-29) secondary terminals.
Set multimeter for ohms and check for continuity between secondary terminals A1 and A2, B1 and B2, and C1 and
C 2.
If continuity is not present, current transformer is defective. Notify next higher level of maintenance.
If continuity is present, connect electrical leads to secondary terminals and remove tags.
Close output box access door.
Connect negative battery cable and close battery access door.
DROOP CURRENT TRANSFORMER.
Inspection.
Shut down generator set.
Open output box access door.
Inspect droop current transformer (8, FIGURE 2-29) for cracked housing, security, broken wire terminals, loose
or missing hardware, and other damage.
Close output box access door.
2-139